            圖124,20000m 3 Calculation sheet for fire sprinkler water of LNG full capacity tank - Doer equipment

            Classification:Forum PublishTime:2019-11-20 14:13:06

            20000m 3 Calculation sheet for fire sprinkler water of LNG full capacity tank


            1. 20000m 3 Standard specifications and basis adopted in the design of fire sprinkler water calculation sheet of LNG full capacity tank


            1) Code for fire protection design of buildings (gb50016-2014)


            2) Code for fire protection design of petrochemical enterprises (GB50160-2008)


            3) code for design of water spray fire extinguishing system (GB50219-2014)


            4) Code for fire protection design of petroleum and natural gas engineering (gb50183-2004)


            2 design scope


            Protect and cool the LNG storage tank.


            Design and calculation of 3 water spray system


            3.1 calculation of wall surface area of LNG storage tank


            Diameter of outer cylinder of LNG storage tank ? = 36m, height h = 26.5m


            Surface area of LNG tank wall S1 = π · D × H =π × thirty-six × 26.5m2 = 2997 m2


            The top cover of LNG storage tank is spherical, with radius r = 30.6m and height h = 5.85m


            Surface area of LNG tank top cover S2 = 2 π · R × H =2π × thirty point six × 5.85m2 =1125 m2


            3.2 calculation of spray water volume of LNG storage tank


            Spray water spray intensity of 3.2. 1 LNG storage tank


            According to the specification:


            Water spray intensity for LNG tank wall design: Q1 = 2.5 L/min. M2 (coefficient derived from GB50219-2014)


            Water spray intensity for LNG tank roof design: Q2 = 4 L/min. M2 (coefficient derived from GB50219-2014)


            Minimum working pressure of water mist nozzle: 0.2MPa


            Duration: 6 h


            3.2.2 calculation of spray water volume of LNG storage tank


            Calculated water volume of LNG storage tank wall: Q1 = S1 × q1=7500 L/min


            Calculated water volume on the top of LNG storage tank: Q2 = S2 × q2 = 4500 L/min


            Total spraying water volume: q = Q1 + Q2 = 12000 L / min


            3.3 calculation of nozzle quantity of LNG storage tank


            3.3.1 flow of single water mist nozzle


            q=K·(10P)1/2


            Q ---- flow of each water mist nozzle, L / min


            K ---- flow coefficient of water mist nozzle


            P -- working pressure at the most unfavorable point of water mist nozzle, MPa


            The type of sprinkler used in the tank wall is ZSTMB-40-120, spray angle of spray nozzle.


            ? =120 ?


            Flow coefficient: k = 40; P takes the minimum value: P = 0.2MPa


            q=K·(10P)1/2=56.6 L/min


            The type of sprinkler used in the roof of this project is ZSTWC-28-120, spray angle of spray nozzle.


            ? =120 ?


            Flow coefficient: k = 28; P takes the minimum value: P = 0.2MPa


            q=K·(10P)1/2=39.6 L/min


            3.3.2 calculation of nozzle quantity


            1. Number of nozzles calculated by water volume:


            Number of tank wall nozzles: N1 = Q1 / Q = 7500 / 56.6 = 132.5


            Number of nozzles on tank top: N2 = Q2 / Q = 4500 / 39.6 = 113.6


            To sum up: the number of top nozzles: 114, the number of tank wall nozzles: 134, a total of 248.