            121,20000m 3 Calculation of maximum make-up gas volume of LNG full capacity tank - Doer equipment

            Classification:Forum PublishTime:2019-11-19 14:41:09

            20000m 3 Calculation of maximum make-up gas volume of LNG full capacity tank


            twenty thousand 3 Determination of gas make-up volume of LNG full capacity tank


            The amount of gas generated under the following conditions shall be considered for supplement;


            (1) LNG pump outgoing


            (2) Bog fan suction


            (3) Atmospheric pressure rise


            In normal operation of LNG low-temperature and atmospheric pressure storage tank, these three situations causing negative pressure of storage tank may occur. Under the three working conditions, the sum of air replenishment is the maximum air replenishment of storage tank.


            1、 Air replenishment caused by LNG submerged pump


            The flow of submersible pump is 450m 3/ h. The storage tank is equipped with two submerged pumps. Doer to the start of the submerged pump, the required air make-up volume of the side storage tank is:


            F1=2 × four hundred and fifty × 1.05=945m 3/ h


            Where:


            450 - flow of submersible pump, M 3/ h


            1.05 - coefficient


            2 - two submersible pumps


            2、 Air replenishment caused by bog compressor


            The gas volume of bog compressor is assumed to be 2500nm at full load 3/ h. Then the storage tank needs air replenishment Doer  to the start of bog compressor


            The quantity is:


            F2=2500 × 1.05=2625m 3/ h


            Where:


            1600 - flow of bog compressor, M 3/ h


            1.05 - coefficient


            3、 Air replenishment caused by atmospheric pressure rise


            The air replenishment capacity with local atmospheric pressure of 97kpa is:


            F3=13633/97 × 1.5=210.8m 3/ h


            Where:


            13633 - maximum volume of gas phase space, M 3


            1.5 - ratio


            97 - atmospheric pressure kPa


            Maximum air make-up volume of storage tank:


            F=F1+F2+F3=945+2625+210.8=3780.8m 3/ h


            Conclusion: the air replenishment capacity of the storage tank is 3780.8m 3/ h. This value is used as the basis for the selection of suction valve and air replenishment device of storage tank